- Robust construction, precise positioning, reliable performance
- Wide range of applications & control systems
- Compact internal arrangement
- Modulating control options can be installed on the site
- Local control options for easy commissioining and emergency operation
Model |
| 04 | 06 | 08 | 10 | 12 | 20 | 25 |
Thrust force | kN | 4 | 6 | 8 | 10 | 12 | 20 | 25 |
Stroke | mm | 40 | 40 | 50 | 50 | 50 | 100 | 100 |
Manual override |
| Handwheel with switchable declutchable lever |
Cable entry |
| 2 - 3/4' PF |
Ambient temperature |
| -20 +70 ℃ |
Position indication |
| Scale on pillar indicated by indicator |
Mounting direction |
| Any direction except for heading downward |
Housing |
| Aluminum alloy hard anodized for anti-corrosion |
Positioning speed | mm / sec | Refer to individual technical data sheet |
Power supply |
| 24 VDC, Single phase (110 / 220 VAC), 3phase (380 / 440VAC) |
Current draw |
| Refer to individual technical data sheet |
Motor protection |
| Themal protector (Class F) |
Operating mode | S2 | Max. 30 Min | Max. 30 Min |
| S4 | 50% ED-1200 c/h | 50% ED-800 c/h |
Weight | Kgs | 7 | 8 | 15 | 16 | 17 | 20 | 22 |
Valve Stem threads | mm | M20 (Max) | M20 (Max) | M20 (Max) | M20 (Max) | M20 (Max) | M24 (Max) | M24 (Max) |
PCD on flange | mm | 100 | 100 | 100 | 100 | 100 | 150 | 150 |
Pillar Threads |
| M16 | M16 | M16 | M16 | M16 | M20 | M20 |
Pillar material |
| Stainless steel, carbon steel with special surface treatment |
|